ILLUSTRATIVE EXECUTION SCOPE · REPRESENTATIVE PROJECT FRAMEWORK · AE-08
Transformer Oil Filtration, BDV & Routine Testing
Representative framework for on-site vacuum dehydration filtration and diagnostic testing of mineral insulating oil in operational distribution transformers to restore dielectric strength and prevent winding failure.
Framework Disclosure:
AE-08 is published as an Illustrative Execution Scope / Representative Project Framework detailing AAROHAN ELECTRICALS' standardized execution sequence, applicable IS/IEC standards, and handover deliverables.
Division E5 · Preventive Maintenance
Technical Framework Parameters
| Governing Standard | IS 1866 & IS 335 Insulating Oil Maintenance |
| Target BDV Post-Filtration | ≥ 60 kV (2.5 mm Gap per IS 6792) |
| Equipment Used | High-Vacuum Streamline Oil Filtration Machine |
| Key Checks | BDV, Acidity, Moisture, Silica Gel & Gaskets |
EXECUTION & TESTING DELIVERABLES
Standardized Site Execution Sequence
- Pre-filtration oil sampling & Breakdown Voltage (BDV) baseline measurement
- Hot-oil circulation through high-vacuum dehydration & micro-filtration plant
- Breather silica gel replacement, oil level top-up (IS 335 oil) & gasket leak arrest
- Buchholz relay, WTI/OTI dial verification & bushing terminal torque check
- Post-filtration BDV test certificate & transformer health report handover