Preventive Electrical Maintenance & Infrared Thermography
How live thermal imaging detects loose busbar joints, phase imbalances, and failing breaker contacts before they escalate into unplanned factory shutdowns or electrical fires.
Seeing Hidden Faults Under Live Load
Over 70% of industrial switchboard failures begin as high-resistance joints—caused by thermal expansion/contraction, vibration, or oxidized aluminium lugs. Before a termination melts or flashes over, it generates localized heat invisible to the naked eye but immediately obvious on a calibrated Infrared (IR) Thermography camera.
Severity Grading During Live IR Scans
- ΔT 1°C – 10°C above reference phase: Early anomaly—log and schedule tightening during the next routine shutdown.
- ΔT 10°C – 20°C above reference phase: Probable deficiency—re-terminate, clean contact surfaces, and apply anti-oxide compound at earliest opportunity.
- ΔT > 20°C – 40°C+: Critical hotspot—immediate load reduction and urgent shutdown rectification required to prevent arc fault or fire.
Combining Thermography with Annual Shutdown Servicing
Pair live IR thermography with scheduled annual shutdown maintenance: vacuum cleaning of panels, ACB/VCB contact servicing, torque-marking all busbar joints, and verifying protective relay trip coils.